KIPOR Inverter Generator Troubleshooting Guide
Problem with your Kipor Inverter generator? Use this problem-solving guide to diagnose possible causes and find solutions.
Section 1- Fuel related problems
Fuel Leak
- Fuel flow
- Stepping motor
- Valve adjustment
Section 2- Generator won’t start
No Start, Cranks, has spark & fuel.
- Choke pin
- Alternator
- Ignition timing
Section 3- No Start, no spark
No Start, Cranks, has no spark.
- Low oil switch
- Spark plug
- Ignition winding
- Ignition coil
Section 4-_No Start, no crank (3000-3500Ti only)
No start- no crank
- Battery low ( does not hold a charge)
- No electric start
Section 5- No AC Output (Inverter series)
1. No AC
Section 1
- Fuel Leak
For the 3000/3500Ti, it could be the valve or it could be the tank leaking between the brass fitting and the plastic tank. Both are replaceable. Determine which is leaking and either part is replaceable.
For all generators, check all fuel lines, valve, pump and carburetor
- Fuel Flow. Open the drain screw on the bottom of the carburetor, do you get a steady flow of fuel? If so, there is no blockage. If no fuel flow, a blockage may be the case. It is possible that you have a partial blockage which allows fuel to flow to the carb, giving the appearance of a steady supply, when in fact it is there but is not enough to meet the demand of the engine. Check for kinks in the fuel line.
It is also possible that there is a blockage in the carb. Try removing the bowl on the bottom of the carb and then removing the float and turning on the fuel. This will allow fuel to flow freely thru the carb. This is a very simple process. However, it may be easier to remove the carburetor first. Be careful to not damage the gasket. Clean the parts and replace them and try again to see if the unit will run properly. It could also be a plugged fuel filter. For the 1000 and 2000Ti, it is located in the gas tank where the fuel line is connected. For the 3000Ti you have to take the fuel valve off and it should come out attached to the valve.
For 1000 and 2000Ti, there is a vacuum gas pump. This pump is activated by a vacuum tube connected to the motor housing situated under the carburetor. Make sure that this tube is connected properly.
- Stepping Motor (Electric Throttle Actuator) Does the stepping motor respond when the inverter module is trying to change the engine speed when more load is applied? Does the stepping motor try to adjust the carb and is unable to or does the carb respond properly to the stepping motor but it still makes no difference? Depending on your answer, it could be the stepping motor or the carb. Spaying WD40 on the linkage and moving it manually might free it up.
Measuring the resistance of stepping motor leading wires

Kipor Inverter Generator Test motor
Specified resistance | 1 and 3 45~55Ω |
2 and 4 45~55Ω |
Replace the stepping motor if the resistance value exceeds the specified range.
Result: Resistance 1 and 3: Resistance 2 and 4:
- Valves. It is also possible that they have improperly adjusted valves. The required clearance is listed in the owner’s manual. Check and adjust if necessary.
Section 2
No Start, Cranks, has spark & fuel.
Do any lights come on while trying to start? If so, which ones?
Yes: No:
Does it “fire” and begin to run, and then die? Or does it never “fire”?
- Choke pin (3000-3500Ti only). It’s possible that the choke pin that fell out. Look under the choke plate for a pin operating the choke mechanism. If not, change the choke plate and the choke cable.
- Alternator. It could be the alternator. At the inverter, disconnect the large 6p plug that has only 5 wires. With the meter in “Diode Checking” mode, check continuity between the two white wires (pins 3 & 6). Reading must be 0.000.
- Ignition Timing. It could be ignition timing. Does it backfire or occasionally fire and then die? This cannot currently be checked without disassembly. But if it occasionally backfires, it is a likely the cause.
Yes: No:
Section 3
No Start, Cranks, has no spark.
For 1000-2000Ti
Do you hear a click when you turn the engine switch to on?
Yes: No:
If no, the microswitch is not operating properly. It could be a wire stopping it from moving or could be dirty. Clean with a non-flammable pressurized cleaner like electrical contact cleaner. If it still doesn’t operate, change the microswitch.
For all models
Do any lights come on while trying to start?
Yes: No: Which one:
- Low Oil Switch. It could be the low oil switch if the low oil light is coming on and the unit will not start. The oil switch might be stuck. 1- Check the oil level. 2- Unplug the oil switch and run the engine for 2 minutes. 3- Reconnect the oil switch with the engine running. 4- Check for a damaged wire (shorting to the ground). The wire is orange coming out of the ignition module. It connects to a yellow wire near the motor that passes thru the crankcase. 5- Remove the control panel and disconnect the 10p plug that goes into the back of the ignition module. Check for continuity between the orange wire and ground. There should be none. It should show O.L. for “Open Line”. If there is continuity, either the wire is shorted or pinched somewhere, or the switch is faulty
Low oil switch connector for 1000-2000Ti Low oil switch connector for 3500Ti older Orange –Yellow/green. green model-connectors. Right side under
Bottom right door opened the starter.
Low oil switch connector for 3000Ti new model. Orange wires- bottom right behind the battery.
- Spark plug. Check, adjust or change the spark plug.
- Ignition Windings. It could be the ignition system. Remove the control panel and unplug the 10p connector that goes to the ignition module (module with 3 lights). Check continuity between ground and green. There should be continuity. Check continuity between ground and yellow.
There should be in the area of 86 ohms resistance. If either or both of these are faulty, there could be a loose wire or bad ignition winding. This requires complete disassembly.
Result: Readings: Ground and green: Ground and yellow:
- Ignition Coil. Unplug the 10p connector that goes to the ignition module (module with 3 lights). To check the primary side of the ignition coil, check continuity between ground and blue wire. There should be reading between 0.7 and 3.5 ohms. To check the secondary side of the ignition coil, unplug the spark plug wire and check continuity between the blue wire and spark plug wire. There should be reading between 12.0 and 21.0 k-ohms. If either or both of these are faulty, there could be a loose wire or bad ignition coil. For 1000 and 2000Ti the coil can be changed. The 3000/3500Ti requires complete disassembly.
Result: Readings: Ground and blue: Blue and spark plug wire:
- Ignition module. If all of the above is correct it could be the ignition module. (Module with 3 lights) We have no tests for this module. Change the module.
Section 4
No Start, no crank. (3000-3500Ti only)
Check the battery voltage. You should read 12-14 VDC. If not, charge the battery and try starting.
Check battery connections. They must be clean and tight.
Check 2p connector just inside the door. It must be plugged in securely.
Check voltage at the starter relay, before cranking. There should be voltage only at the large post that has the battery cable attached to it. If there is no voltage, check the cable and connections. Turn the key to the start position and check for voltage at the second large terminal (Starter side)
If voltage is not present at both large posts (12–14 volts), either the relay or the ignition switch is faulty. Disconnect the 2p plug, near the door and check for voltage between the yellow wire and ground making sure the switch is turned to the start position. If voltage is present replace the start relay. If no voltage is present replace the ignition switch.
If voltage is present at both large posts, the problem is in the starter motor or the cable leading to it. If the first test for the relay checks out OK, make sure the 2p plug is securely reconnected and check voltage at the large post that is connected to the cable that goes to the starter motor while cranking. If there is no voltage, the relay is faulty. Replace it. If there is voltage, and all of the above items are all working properly, the problem is in the starter motor or the cable leading to it. Remove the end panel and check for secure connections and/or damage in the cable. If no damage is found and connections are good, remove the cabinet and check the connection and voltage at the starter. If there is correct voltage and the connection is good, and no cranking, the starter motor is faulty
Battery low (does not hold a charge)
If the battery will not hold voltage, either the battery or the 12vdc charge circuit is faulty. Check the battery using a battery tester. If faulty, replace the battery. If good, unplug the battery, start the engine with the pull cord and test the voltage at the battery connectors. It should read 12.5 to 13.5volts. If not, remove the control panel and check the fuse on the purple wire. If the fuse is good, the 12vdc regulator is the likely culprit. Either can be replaced.
No Electric Start.
Check the battery voltage. Should be12-14 VDC, if not, charge the battery and try starting. Check battery connections. They must be clean and tight.
Check the plug connections on the back of the ignition switch.
-
- If all of the above are correct you will need to remove the front control end panel and check 2p connector, it must be plugged in securely. (fig. 1)

Kipor Inverter connection test

Kipor inverter generater starter relay test

Kipor inverter generator wiring problem test
-
- Check voltage at the starter relay (bottom left side fig. 2) before cranking. There should be (12–14 volts) only at the large post that has the battery cable attached to it- Fig. 3-A. If there is no voltage, check the cable and connections. Turn the key to the start position and check for voltage at the starter terminal (fig. 3-B)

Kipor Inverter Generator terminal connection test
-
- If voltage is not present (12–14 volts) either the relay or the ignition switch is faulty. Disconnect the 2p plug, near the door and check for voltage between the yellow wire (fig. 4-A) and the yellow w/green strip, ground wire (fig. 4-B)

Kipor inverter generator wire test
-
- there should be (12–14 volts) when the ignition switch in the start position. If voltage is present replace the start relay. If no voltage is present replace the ignition switch. If voltage is present at both large posts, the problem is in the starter motor or the cable leading to it.
- If the first tests for the relay and ignition switch checks out OK, then make sure the 2p plug is securely reconnected. Remove the cabinet and check the connection and voltage at the starter. If there is no voltage, check the cable and connection. If there is voltage and the connection is good, and no cranking, the starter motor is faulty,
Section 5
1- No AC Output (Inverter series)
This could be a loose wire from the inverter to the receptacles. On KGE3000Ti, remove the end panel and look down by the lower, right corner, as they face the control panel. On the KGE1000 and 2000Ti, this is located behind the control panel. Check to see if the red and black wires are securely plugged in and the wires are securely attached to the receptacles.

Kipor inverter generator black and red wire testing

Kipor inverter generator testing for problems
If no problems are found on the steps above;
Next, there is a large 6 position connector that actually has only 5 wires in it, that plugs into the back of the inverter.

Kipor inverter generator voltage checking
Unplug the connector from the inverter and start the engine, check voltage between pins 1 & 4, between pins 2 & 4, and between pins 1 & 2. They should be approximately 300vac at each test. If one or more of the three tests fail, the problem is either a damaged wire harness or a defective alternator. If the wire harness is the problem, look for and repair the damage. If the alternator is the problem, the stator and rotor will need to be replaced. If all three tests are OK, the problem is likely the inverter.